Technical data
|
|
Electrical data
|
|
Nominal voltage
|
AC/DC 24 V
|
Nominal voltage frequency
|
50/60 Hz
|
Nominal voltage range
|
AC 19.2...28.8 V / DC 21.6...28.8 V
|
Power consumption in operation
|
5.5 W
|
Power consumption in rest position
|
3 W
|
Power consumption for wire sizing
|
8.5 VA
|
Connection supply / control
|
Cable 1 m, 4 x 0.75 mm²
|
Parallel operation
|
Yes (note the performance data)
|
Functional data
|
|
Torque motor
|
20 Nm
|
Torque fail-safe
|
20 Nm
|
Operating range Y
|
2...10 V
|
Input Impedance
|
100 kΩ
|
Position feedback U
|
2...10 V
|
Position feedback U note
|
Max. 0.5 mA
|
Position accuracy
|
±5%
|
Direction of motion motor
|
Y = 0 (0 V = A – AB = 0%)
|
Direction of motion fail-safe
|
Deenergised NC, valve closed (A – AB = 0%)
|
Manual override
|
by means of hand crank and locking switch
|
Running time motor
|
90 s / 90°
|
Running time fail-safe
|
<20 s @ -20...50°C / <60 s @ -30°C
|
Sound power level, motor
|
45 dB(A)
|
Position indication
|
Mechanical
|
Service life
|
Min. 60'000 fail-safe positions
|
Safety data
|
|
Protection class IEC/EN
|
III, Safety Extra-Low Voltage (SELV)
|
Power source UL
|
Class 2 Supply
|
Degree of protection IEC/EN
|
IP54
|
Degree of protection NEMA/UL
|
NEMA 2
|
Enclosure
|
UL Enclosure Type 2
|
EMC
|
CE according to 2014/30/EU
|
Certification IEC/EN
|
IEC/EN 60730-1 and IEC/EN 60730-2-14
|
UL Approval
|
cULus according to UL60730-1A, UL60730-2-14 and CAN/CSA E60730-1
The UL marking on the actuator depends on the production site, the device is UL-compliant in any case
|
Mode of operation
|
Type 1.AA
|
Rated impulse voltage supply / control
|
0.8 kV
|
Pollution degree
|
3
|
Ambient humidity
|
Max. 95% RH, non-condensing
|
Ambient temperature
|
-30...50°C [-22...122°F]
|
Storage temperature
|
-40...80°C [-40...176°F]
|
Servicing
|
maintenance-free
|
Weight
|
|
Weight
|
2.2 kg
|