Specification
|
Description
|
Product switch action
|
SPDT
|
Pressure connection
|
7/16-20 UNF for 6 mm (1/4 in. SAE external flare fitting), or 914 mm (36 in.) capillary with 6 mm (1/4 in.) flare fitting
|
Ambient conditions
|
Temperature: -40°C to 60ºC (-40°F to 140ºF)
Humidity: 0% to 95% R.H. non-condensing
|
Enclosure
|
Type 1: cast aluminum
|
Dimensions
|
Type 1 enclosure: 88 mm x 80 mm x 53 mm
|
(H x W x D)
|
(3.48 in. x 3.15 in x 2.09 in.)
|
Approximate shipping weight
|
Individual pack: (Type 1 enclosure): 0.5 kg (1.1 lbs)
Bulk pack: (Type 1 enclosure in multiples of 35 controls): 19 kg (41.88 lbs)
|
Compliance
|
cULus Listed; UL 60730, File SA516
|
P77 for low pressure applications
|
|
Purpose of control
|
Pressure operating control: automatic reset controls
Pressure cut-out: manual reset controls
|
Construction of control
|
Electromechanical
|
Number of cycles
|
Automatic: 30,000 cycles
Manual reset: 6,000 cycles
|
Method of mounting control
|
Independently-mounted control
|
Type 1 or Type 2 action
|
Automatic: Type 1; Type 1.C; micro-interruption
Manual reset: Type 2
|
Pollution degree
|
Category 3
|
Heat and fire resistance category
|
N/A
|
Rated impulse voltage
|
4,000 V
|
Ball pressure temperature
|
N/A
|
Field wiring rating
|
90°C (194°F)
|
Maximum overpressure
|
20 bar (290 psi)
|
Cover screw torque requirements
|
Tighten enclosure screws to: 1.1–1.4 N·m (10–12 in·lb)
|
P77 for high pressure applications
|
|
Purpose of control
|
Pressure operating control: automatic reset controls
Pressure cut-out: manual reset controls
|
Construction of control
|
Electromechanical
|
Number of cycles
|
Automatic: 30,000 cycles
Manual reset: 6,000 cycles
|
Method of mounting control
|
Independently-mounted control
|
Type 1 or Type 2 action
|
Automatic: Type 1; Type 1.C; micro-interruption
Manual reset: Type 2
|
Pollution degree
|
Category 3
|
Heat and fire resistance category
|
N/A
|
Rated impulse voltage
|
4,000 V
|
Ball pressure temperature
|
N/A
|
Field wiring rating
|
90°C (194°F)
|
Maximum overpressure
|
33 bar (479 psi)
|
Cover screw torque requirements
|
Tighten enclosure screws to: 1.1–1.4 N·m (10–12 in·lb)
|